Air leaving the pad–
Cooling achieved–
Air at the fans (typical)–
Drag to rotate, scroll or pinch to zoom

The pad formula

Evaporative cooling can at best bring air down to its wet bulb temperature. Pad efficiency says how much of that gap a pad closes: leaving temperature = dry bulb minus efficiency x (dry bulb minus wet bulb).

A well kept system can reach about 85 percent efficiency. Clogged, dry or poorly sized pads fall well below that.

Try it: keep the air at 35 °C and move the wet bulb from 18 to 29 °C. On the dry day the pad cools air by more than 13 degrees; on the humid day, by less than 5. Then drop the efficiency to 50 percent to see what a neglected pad costs.

Why the fan end is warmer

Sunlight and the crop keep adding heat as air crosses the house. The third readout adds a typical 4 °C rise between pads and fans, a rule of thumb rather than a calculation for your house. Keeping the pad to fan distance short keeps that rise small.

Where Avid uses this

Avid's founder began his career as an HVAC apprentice at 16, and the same psychrometrics behind building cooling drive greenhouse pad and fan design.

How to cite this model

Avid Solutions International. (2026, November 11). How a greenhouse cools with wet pads [Interactive 3D model]. Avid Field Lab. https://avidsolutionsintl.com/explore/greenhouse-pad-fan