Fresh air delivered at–
Energy recovered–
Still to heat or cool–
Drag to rotate, scroll or pinch to zoom

Effectiveness

Sensible effectiveness is the fraction of the indoor to outdoor temperature difference that the core recovers. Supply temperature = T outdoor + effectiveness x (T indoor minus T outdoor). With 0 °C outside, 21 °C inside and 70 percent effectiveness, fresh air arrives at about 14.7 °C.

Recovered power is air mass flow times specific heat times the temperature rise of the fresh air, using 1.2 kg/m³ and 1.006 kJ/kg·K. This model treats sensible heat only and ignores the moisture an ERV core also exchanges, so it understates savings in humid weather.

Try it: set the outdoor temperature to minus 20 °C and airflow to 150 L/s. Energy recovered climbs past 5 kW, heat that a plain exhaust fan would simply throw away.

Why tight houses need them

Modern homes are sealed so well that they need mechanical ventilation for healthy indoor air. Balanced ventilation with energy recovery provides that fresh air while keeping most of the heating and cooling energy indoors.